Summer outdoor and return air

An air handler draws in warm outdoor air and mixes it with cooler return air ahead of a coil. Which stream contributes more moisture per kilogram of dry air?

Summer inlet and outlet conditions
Property1 · Return2 · OutdoorOutlet
Dry bulb (°C)24.0035.0028.31
RH (%)50.044.749.16
Actual flow (L/s)7,5005,00012,500.2
Vapour (g/kg dry air)9.3115.8511.85

The outdoor RH is lower, yet each kilogram of outdoor dry air carries about 70% more water vapour. The two flows supply 8.77 and 5.58 kg/s of dry air, respectively. Weighting the two humidity ratios by those flows gives the outlet’s 11.85 g/kg.

The mixed-air dew point is 16.63 °C. A coil surface below that temperature can collect condensate even though mixing alone produced none. To reproduce the outdoor state from a wet-bulb reading, change Stream 2 to wet bulb and enter 24.99 °C.

Load the summer example →

Winter outdoor-air fraction

A winter intake provides one quarter of the actual inlet volume. How close is the mixed temperature to a simple 25% outdoor-air estimate?

Winter inlet and outlet conditions
Property1 · Outdoor2 · ReturnOutlet
Dry bulb (°C)0.0022.0016.18
RH (%)80.040.049.33
Actual flow (L/s)2,5007,50010,000.1
Dry-air flow (kg/s)3.218.8712.08

A volume-weighted temperature would be 16.50 °C. Cold air is denser, so the intake contributes 26.59% of the dry-air mass. The energy balance gives 16.18 °C, about 0.32 °C colder. Even at 80% RH, that cold stream carries only 3.02 g/kg of vapour. Bringing it indoors lowers the humidity ratio of the 6.57 g/kg return air to 5.63 g/kg.

Load the winter example →

Fog from two saturated streams

Mix 5,000 L/s of saturated air at 3 °C with 5,000 L/s of saturated air at 42 °C. The curved saturation boundary makes it possible for two individually valid inlets to yield a supersaturated trial state.

Trial state and equilibrium outlet for the fog example
PropertyVirtual mixFinal mix
Dry bulb (°C)21.3228.07
RH (%)167.02100.00
Vapour (g/kg dry air)27.17824.250
Gas enthalpy (kJ/kg dry air)90.5090.15

The virtual result assumes all water remains vapour. Condensation releases heat, bringing the saturated outlet to 28.07 °C. The decrease in vapour is 2.928 g per kilogram of dry air. At 11.476 kg/s of dry air, the equilibrium condensate rate is

0.002928 × 11.476 × 3,600 ≈ 121 kg/h

This is the mass of condensed water produced in the ideal mix. The amount reaching a drain depends on how much separates from the air and how much remains suspended as fog.

Load the condensation example →

Mixing return air with a cooler stream

Follow a fourth case from actual inlet flows through the dry-air mass split to the final mixed state. This example uses measured pressure and a 2:1 inlet volume ratio.

Work through the return-air example →

Explore the calculation method and assumptions →