Summer outdoor and return air
An air handler draws in warm outdoor air and mixes it with cooler return air ahead of a coil. Which stream contributes more moisture per kilogram of dry air?
| Property | 1 · Return | 2 · Outdoor | Outlet |
|---|---|---|---|
| Dry bulb (°C) | 24.00 | 35.00 | 28.31 |
| RH (%) | 50.0 | 44.7 | 49.16 |
| Actual flow (L/s) | 7,500 | 5,000 | 12,500.2 |
| Vapour (g/kg dry air) | 9.31 | 15.85 | 11.85 |
The outdoor RH is lower, yet each kilogram of outdoor dry air carries about 70% more water vapour. The two flows supply 8.77 and 5.58 kg/s of dry air, respectively. Weighting the two humidity ratios by those flows gives the outlet’s 11.85 g/kg.
The mixed-air dew point is 16.63 °C. A coil surface below that temperature can collect condensate even though mixing alone produced none. To reproduce the outdoor state from a wet-bulb reading, change Stream 2 to wet bulb and enter 24.99 °C.
Winter outdoor-air fraction
A winter intake provides one quarter of the actual inlet volume. How close is the mixed temperature to a simple 25% outdoor-air estimate?
| Property | 1 · Outdoor | 2 · Return | Outlet |
|---|---|---|---|
| Dry bulb (°C) | 0.00 | 22.00 | 16.18 |
| RH (%) | 80.0 | 40.0 | 49.33 |
| Actual flow (L/s) | 2,500 | 7,500 | 10,000.1 |
| Dry-air flow (kg/s) | 3.21 | 8.87 | 12.08 |
A volume-weighted temperature would be 16.50 °C. Cold air is denser, so the intake contributes 26.59% of the dry-air mass. The energy balance gives 16.18 °C, about 0.32 °C colder. Even at 80% RH, that cold stream carries only 3.02 g/kg of vapour. Bringing it indoors lowers the humidity ratio of the 6.57 g/kg return air to 5.63 g/kg.
Fog from two saturated streams
Mix 5,000 L/s of saturated air at 3 °C with 5,000 L/s of saturated air at 42 °C. The curved saturation boundary makes it possible for two individually valid inlets to yield a supersaturated trial state.
| Property | Virtual mix | Final mix |
|---|---|---|
| Dry bulb (°C) | 21.32 | 28.07 |
| RH (%) | 167.02 | 100.00 |
| Vapour (g/kg dry air) | 27.178 | 24.250 |
| Gas enthalpy (kJ/kg dry air) | 90.50 | 90.15 |
The virtual result assumes all water remains vapour. Condensation releases heat, bringing the saturated outlet to 28.07 °C. The decrease in vapour is 2.928 g per kilogram of dry air. At 11.476 kg/s of dry air, the equilibrium condensate rate is
0.002928 × 11.476 × 3,600 ≈ 121 kg/h
This is the mass of condensed water produced in the ideal mix. The amount reaching a drain depends on how much separates from the air and how much remains suspended as fog.
Mixing return air with a cooler stream
Follow a fourth case from actual inlet flows through the dry-air mass split to the final mixed state. This example uses measured pressure and a 2:1 inlet volume ratio.