Choose the inlet conditions

Take the temperature, moisture reading and airflow for each stream at the point where it enters the mixing box. A supply fan or a coil between a sensor and that inlet can change the state before mixing begins.

Inputs and their measurement basis
InputHow to enter it
Temperature and moistureEnter dry-bulb temperature in °C. For each stream, choose either RH in percent or thermodynamic wet-bulb temperature in °C. Wet bulb can equal dry bulb at saturation.
AirflowUse actual L/s at each stream’s measured conditions. If the flow is quoted at standard conditions, first convert it using the reference density specified for that reading.
PressureBoth streams share one absolute pressure. Enter local station pressure in kPa, or use elevation in metres for a standard-atmosphere estimate. A weather report’s sea-level-adjusted pressure requires conversion before use at elevation.

Weight the streams by dry-air mass

A litre of cold air can carry more dry-air mass than a litre of warm air. For each inlet, the calculator finds moist-air density ρ and humidity ratio W from the inlet conditions. Humidity ratio is kilograms of water vapour per kilogram of dry air. With actual volume flow Q in m³/s, the dry-air flow in kg/s is

ṁda = ρ Q / (1 + W)

Let x be Stream 1’s share of the combined dry-air mass flow. The water carried in by both streams and their specific enthalpies h give two weighted averages, each on a dry-air basis.

Win = x W1 + (1 − x) W2
hin = x h1 + (1 − x) h2

The solver first keeps all inlet water in the gas phase and finds the temperature with those two properties. This is the virtual mix. If it lies at or below saturation, it is also the final outlet. Relative humidity is calculated at that outlet temperature.

When the mixture crosses saturation

A virtual mix above the saturation curve contains more vapour than can remain in equilibrium. The solver finds a new temperature at which the gas is saturated and the gas plus condensed water together carry the incoming enthalpy.

At that temperature the difference between the incoming humidity ratio and the final gas humidity ratio gives the condensed mass per kilogram of dry air. Multiplying by total dry-air flow gives the condensate rate. The displayed gas enthalpy excludes the energy carried by the condensate.

The liquid option uses liquid-water enthalpy for the condensed phase. The ice option uses ice enthalpy below 0 °C and liquid-water enthalpy above freezing. PsychroLib evaluates saturation over ice below the water triple point in both modes. At freezing, the ice option can produce liquid and ice together to close the energy balance. These are equilibrium assumptions. Actual droplet formation, freezing, carryover and drainage also depend on equipment and contact time.

Follow the water balance for two saturated streams →

Read the chart and check the result

The horizontal axis is dry-bulb temperature. The vertical axis is grams of water vapour per kilogram of dry air. Each curved line follows a constant relative humidity at the selected pressure. For an unsaturated mix, the virtual and final markers coincide. For a condensing mix, follow the final marker to the saturation curve.

  • Check dry-air flow. The final dry-air mass flow should equal the sum of the two inlets. Actual outlet L/s uses the outlet density and can differ from the sum of the incoming L/s.
  • Check water. When mixing produces no condensate, the outlet humidity ratio lies between the inlet values. Where condensate forms, include the condensed mass when checking the water balance.
  • Check the measurement location. The result represents a fully mixed, steady outlet with no heat exchange, fan work or pressure drop across the box. A probe in a cold streak near the dampers can read well below the mixed temperature.

Compare mass flow and volume flow in a winter mixing box →