Match the humidity input to the reading

For each inlet, pair the ordinary air temperature (dry bulb) with one moisture reading taken at the same location. Choose relative humidity for a reading in percent. Choose wet bulb for a temperature reading from a wet-bulb measurement. You can use a different method for each inlet.

At 26 °C and 101.325 kPa, 50% RH corresponds to a wet bulb of about 18.71 °C. To see the two methods agree, open the example, switch just Stream 1 to wet bulb, enter 18.71, and calculate again. The mixed state reads about 21.19 °C and 57.3% RH with either method. Load the inlet readings.

A wet bulb above the paired dry bulb is physically inconsistent. Check the units, sensor labels and sampling location. If a weather report gives a dew point, entering it as a wet bulb describes a different moisture condition. For the 26 °C example the dew point is about 14.78 °C, almost 4 °C below the wet bulb.

Use airflow at the inlet conditions

Enter each stream’s actual volume in litres per second at its own temperature and pressure. Convert m³/s to L/s by multiplying by 1,000. For example, 0.4 m³/s is 400 L/s. A value labelled “standard” or “normal” volume has already been referred to particular conditions. Check the instrument’s reference temperature and pressure before converting it to actual volume.

The calculator converts each volume to dry-air mass flow. If equal volume readings yield different mass flows, compare the inlet densities in the state table. A colder stream usually carries more dry air per litre under similar pressure and humidity conditions.

Choose the pressure both streams share

Use measured local absolute pressure when available, in kPa. A barometer reading of 965 hPa is 96.5 kPa. Weather reports often give pressure corrected to sea level. Look for station pressure when using data from an elevated site.

If you know only the site elevation, use the elevation option. At 1,000 m it estimates about 89.87 kPa. That estimate represents a standard atmosphere. Actual pressure varies with weather. Pressure affects the conversion of a wet-bulb reading to moisture content and the mass of air moving through a duct.

Read the result within the model’s scope

PsychroMix combines two steady air streams at one pressure and assumes complete mixing without heat exchange with the surroundings. It treats inlet moisture as vapour. A coil, fan heat, water spray or droplets already present at an inlet add effects outside this balance.

If the virtual mixture exceeds saturation, the calculator solves for a saturated final state and a condensed-water rate. The liquid setting uses liquid-water enthalpy. The ice option uses ice enthalpy below freezing and liquid-water enthalpy above it. Ice and liquid can coexist at 0 °C. Both options give the same answer when the mixture stays unsaturated. Compare the virtual and final states.

The property conversions use PsychroLib. Its documentation lists the definitions, units and ASHRAE references for the humidity, wet-bulb and enthalpy calculations. PsychroLib property reference.